YTPY Series Fire High-Temperature Smoke Exhaust Fan
The fire high-temperature smoke exhaust axial flow fan is suitable for conveying media with a temperature up to 280°C and dust content not exceeding 100 mg/m³. Under rated speed and airflow conditions, the total pressure efficiency shall not be less than 70%, and the total pressure deviation shall not exceed ±5% of the rated value.
-
The A-weighted sound pressure level of the fan under rated operating conditions shall not exceed 38 dB(A).
-
The impeller balance accuracy shall not be lower than Grade 5.6.
-
The vibration intensity (root mean square velocity) shall not exceed 6.3 mm/s.
-
The fan shall operate safely for no less than 30 minutes at a temperature of 280°C.
-
The motor shall use high-temperature resistant electromagnetic wire and heat-resistant materials, reaching Class F insulation.
-
It adopts a patented induction-type motor cooling system, improving efficiency and reducing noise, in compliance with GB/T13274-91 and GA211-1999 standards.